Industrial Fan Selection Guide: CFM, Static Pressure & Power Calculations

Most selection errors share a common root cause: the three core parameters — airflow (CFM), static pressure (in. wg), and motor power (HP) — are calculated in isolation instead of as an interdependent system. A fan’s published CFM rating means nothing without knowing the system resistance it will actually face. A motor sized for full-load conditions will burn out when the fan operates at its actual working point. Field surveys of HVAC installations consistently show that the majority of performance shortfalls trace back to fan selection errors made before a single piece of equipment is ordered.

This guide covers the complete fan selection process for engineers, contractors, and facility managers. By the end, you will know how to calculate all three parameters correctly, find the operating point where the fan curve meets your system curve, and select a fan type that matches your application’s requirements — including ATEX-rated hazardous locations, high-temperature processes, and cleanroom environments.

Key Takeaways

  • Industrial fan selection requires three interdependent calculations: CFM, static pressure, and motor power — never treat them independently
  • Start with airflow (CFM) from room volume and air changes per hour (ACH), then calculate static pressure from your duct system, then size the motor
  • The fan’s published performance data is only meaningful at the operating point where its fan curve intersects your system resistance curve
  • Always add a 10–15% safety factor to calculated motor power; oversizing or undersizing both cause serious problems
  • Application-specific requirements — explosion-proof ratings, high-temperature materials, cleanroom turbulence — must be factored in before selecting a fan type

Understanding Fan Selection: The Three Core Parameters

Every industrial fan selection is defined by three values that change together along the fan’s performance curve: airflow (CFM), static pressure (inches of water gauge, in. wg), and brake horsepower (HP). These are not independent specifications — they are three points on a single curve.

Change one, and the other two shift automatically. Select a fan for 20,000 CFM at 1.5 in. wg static pressure, and the fan curve tells you exactly which RPM and HP correspond to that operating point. Move to 25,000 CFM at the same pressure, and RPM and HP change along the curve.

This interdependence is why a fan selected from a manufacturer’s free-delivery CFM rating — without accounting for actual system resistance — almost always underperforms. The fan is rated at zero external resistance. Real ductwork, filters, coils, and outlets create resistance that shifts the operating point away from the catalog condition.

AMCA Standard 210 (Air Movement and Control Association International) defines the standardized laboratory conditions under which all fan performance data is measured. Certified fans are tested in a laboratory with standardized inlets, outlets, and intake configurations. Any deviation from those conditions — which is every real installation — changes the operating point. Understanding this gap between laboratory ratings and field conditions is the foundation of correct fan selection.


Step 1 — Calculate Required Airflow (CFM)

The starting point for every fan selection is airflow, expressed in cubic feet per minute (CFM). Airflow requirements are determined by the space volume and the number of air changes per hour (ACH) appropriate for the application’s purpose.

The CFM formula:

CFM = (Room Volume in cubic feet × ACH) ÷ 60

Where room volume = floor area (sq ft) × ceiling height (ft), and ACH is the number of times the air in the space is replaced per hour.

ACH values vary by application and are governed by standards including ASHRAE 62.1 (Ventilation for Acceptable Indoor Air Quality). The following table provides ACH ranges for common industrial and commercial applications:

ApplicationTypical ACH RangeNotes
Warehouse (general ventilation)4–8Depends on ceiling height and heat load
Light manufacturing / assembly6–10Moderate heat and contaminant load
Heavy manufacturing / welding10–20High heat and particulate load
Cleanroom (ISO 8 / Class 100,000)6–15ISO 14644 governs specific requirements
Cleanroom (ISO 7 / Class 10,000)20–60Laminar flow and HEPA filtration add pressure drop
Parking garage6–8ASHRAE 62.1 for garage ventilation
Commercial kitchen hood100–150Exhaust volume per hood cfm per linear foot
Bathroom / utility exhaust8–15Intermittent or continuous depending on occupancy

Worked example — Warehouse ventilation:

A warehouse measures 100 ft × 100 ft with a 20 ft ceiling. It requires general ventilation at 6 ACH.

  • Room volume = 100 × 100 × 20 = 200,000 cubic feet
  • CFM = (200,000 × 6) ÷ 60 = 20,000 CFM

This 20,000 CFM is the design airflow — the first parameter of fan selection.

Large industrial centrifugal fan installed in a commercial building HVAC system

Common pitfall: Selecting a fan from a catalog based on its free-delivery CFM rating without calculating the actual system resistance. A fan rated at 20,000 CFM in the lab will deliver significantly less in a system with 100 ft of ductwork, multiple bends, a filter bank, and a heating coil. The static pressure those components create must be calculated next.

[INTERNAL-LINK: Axial Fans vs Centrifugal Fans: 7 Key Differences → comparison article on fan types]


Step 2 — Calculate System Static Pressure (in. wg)

Static pressure, measured in inches of water gauge (in. wg), is the resistance the fan must overcome to move air through the duct system and its components. Underestimating static pressure causes the fan to deliver less air than designed. Overestimating it results in an oversized fan that wastes energy and operates inefficiently at part-load.

Static pressure has three components:

2.1 — Friction Loss in Straight Duct

Air moving through straight ductwork loses pressure due to friction against the duct walls. The friction rate (in. wg per 100 ft of duct) depends on duct diameter, air velocity, and the duct material’s roughness coefficient.

For galvanized steel ductwork, friction rates typically range from 0.05 to 0.25 in. wg per 100 ft of straight duct at normal operating velocities. Larger ducts have lower friction rates per foot. The Darcy-Weisbach equation or the ASHRAE Fundamentals Handbook ductwork tables provide precise values for any combination of duct size, airflow, and material.

2.2 — Dynamic Losses at Fittings

Every bend, transition, elbow, and take-off in a duct system creates turbulence that consumes pressure. These are called dynamic losses or minor losses, expressed as equivalent straight duct lengths. A standard 90° elbow in a 12-inch round duct is equivalent to approximately 15–25 ft of straight duct, depending on the radius-to-diameter ratio.

Use fitting loss coefficients from the ASHRAE Fundamentals Handbook, Chapter 21 (Duct Design) or manufacturer catalogs to calculate the equivalent length of each fitting, then add it to the total system length for friction calculation.

2.3 — Component Pressure Drops

Filters, coils, dampers, grilles, and louvers each add a pressure drop that must be included in the total system static pressure calculation.

The most frequently underestimated component is the air filter. A clean pleated filter typically adds 0.05–0.15 in. wg pressure drop at normal face velocities. After extended operation, bypass around a loaded filter can push this to 0.5 in. wg or higher — and a dirty filter that restricts airflow by 20–30% at the same time it increases system resistance. ASHRAE Standard 52.2 (Method of Testing General Ventilation Air-Cleaning Devices) governs filter pressure drop testing and rating.

Heating and cooling coils add 0.2–0.8 in. wg depending on coil face velocity and rows. Dampers (when partially closed for balancing) can add 0.1–0.5 in. wg.

Total system static pressure is the sum of all three components:

Total SP = Friction loss (straight duct) + Dynamic losses (fittings) + Component pressure drops

Typical ranges for common HVAC systems:

System TypeTypical Total Static Pressure
Simple exhaust system (short duct, few fittings)0.5–1.0 in. wg
Standard commercial VAV system1.0–2.0 in. wg
Industrial process exhaust (filters, coils)2.0–4.0 in. wg
Cleanroom HVAC (HEPA filters, reheat coils)3.0–6.0 in. wg
High-speed industrial exhaust (long duct, many bends)4.0–8.0 in. wg

Worked example — continued:

For the warehouse in our example, assume:

  • 100 ft of 24-inch round galvanized duct (friction loss ~0.08 in. wg/100 ft): 0.08 in. wg
  • Six 90° elbows and two tees (estimated dynamic loss equivalent): 0.30 in. wg
  • Intake hood and outlet louver: 0.15 in. wg
  • No filter or coil in this simple exhaust application

Total estimated static pressure = 0.53 in. wg

Industrial ductwork and ventilation system showing duct runs and connections

For a more precise calculation on a complex duct layout, see our detailed guide:

[INTERNAL-LINK: Fan Pressure Loss Calculation: 3-Step Method → fan pressure loss calculation spoke article] Static Pressure Breakdown — Warehouse Ventilation System Components of Total System Resistance at 20,000 CFM Design Condition 0.30 Duct Friction 0.40 Fittings & Bends 0.25 Intake & Outlet Total: 0.95 in. wg ← Total system static pressure (sum of all components) 0.25 0.50 Source: ASHRAE Handbook — Fundamentals, 2021; AMCA 210 Static pressure breakdown for a 20,000 CFM warehouse ventilation system. Fittings and bends represent the largest single component of system resistance in typical duct installations. Values are illustrative for a 100-ft galvanized steel duct system with 8 fittings.


Step 3 — Calculate Motor Power (HP)

With design CFM and static pressure established, the next parameter is motor power. The fan motor must deliver enough brake horsepower to overcome system resistance at the design airflow while maintaining acceptable efficiency.

Fan power formula:

HP = (CFM × Static Pressure) ÷ (6,356 × Fan Efficiency × Motor Efficiency)

Where:

  • CFM = design airflow in cubic feet per minute
  • Static Pressure = total system pressure in in. wg
  • 6,356 = a unit conversion constant combining ft·lbf/min per HP and in. wg to PSF
  • Fan Efficiency = mechanical efficiency of the fan impeller and housing
  • Motor Efficiency = efficiency of the electric motor (typically 0.85–0.95 for NEMA Premium motors)

Fan efficiency varies significantly by type and size:

Fan TypeTypical Peak Mechanical EfficiencyNotes
Axial propeller (cheap, low-pressure)40–60%Suitable only for very low resistance systems
Axial vane-axial60–75%Better for higher pressure applications
Centrifugal forward-curved60–70%Compact, good for clean airstreams
Centrifugal backward-inclined70–80%Widely used in commercial HVAC
Centrifugal airfoil75–85%Highest efficiency among common industrial fans
Plenum fan / housed VAV70–82%LowTip-speed designs for low noise

Motor efficiency matters more than many specifiers realize. NEMA Premium efficiency motors (NEMA MG 1-2021) are typically 1–5 percentage points more efficient than standard efficiency motors, and the additional cost typically pays back in 1–3 years of operation. For a 10 HP motor running 4,000 hours per year, moving from 89% to 94% efficiency saves approximately 600 kWh annually — worth $60–$120 per year at typical industrial electricity rates.

Worked example — continued:

For our warehouse fan at 20,000 CFM and 0.95 in. wg total static pressure:

  • Using a backward-inclined centrifugal fan at 75% peak efficiency
  • Motor efficiency of 91% (NEMA Premium)

HP = (20,000 × 0.95) ÷ (6,356 × 0.75 × 0.91)
HP = 19,000 ÷ 4,338 ≈ 4.4 HP

With a 15% safety factor: 4.4 × 1.15 = 5.1 HP → select a 5 HP motor

The safety factor accounts for motor heating under sustained load, voltage variations, and unexpected system resistance. A 10–15% safety factor is standard practice; exceeding 20% introduces the efficiency penalty of significant part-load operation.

Fan energy context: Industrial fan motors consume a significant share of total HVAC energy in industrial facilities. The U.S. Department of Energy’s industrial assessment data consistently identifies fan system optimization as one of the highest-ROI efficiency opportunities in industrial HVAC — often ranking above boiler controls, lighting upgrades, and compressor optimization in facilities with high ventilation loads. Selecting the right fan and motor for actual operating conditions — not the catalog’s ideal condition — is one of the most impactful decisions in any industrial HVAC project.

[INTERNAL-LINK: Variable Frequency Drive (VFD) Fan Energy Savings: ROI Calculator & 3 Real-World Cases → VFD energy savings spoke article] Fan Motor Energy Breakdown — Typical Industrial Installation 20,000 CFM @ 0.95 in. wg — Backward-Inclined Fan, 75% Efficiency Input Power 5.0 HP Legend Useful Air Work 75% — Air delivered to system Mechanical Loss 10% — Bearing & friction Windage & Seal 8% — Rotor disk friction Drive Loss 5% — Belt/chain efficiency Motor Electrical Loss 2% — Stator & rotor I²R Source: AMCA Engineering Handbook, 2022; NEMA MG 1-2021 Energy breakdown for a backward-inclined centrifugal fan at design conditions. The useful air work represents 75% of input power — the remaining 25% is lost to mechanical friction, windage, drive inefficiency, and motor electrical resistance.


Finding the Operating Point — Fan Curve vs. System Curve

This is the most critical — and most commonly skipped — step in fan selection. The fan curve and the system curve are two separate mathematical relationships. Their intersection is the operating point.

The Fan Curve

A fan curve plots the fan’s performance: CFM on the horizontal axis, static pressure on the vertical axis, at a constant RPM. Each point on the curve represents a possible operating condition. Higher CFM means lower static pressure (and vice versa) along the same curve.

At zero resistance (free delivery), the fan produces its maximum CFM and zero static pressure. As resistance increases, airflow decreases along the curve until the fan reaches its shutoff pressure — maximum static pressure at zero flow.

Multiple fan curves exist at different RPMs. Higher RPM shifts the entire curve upward and to the right (more CFM, more pressure).

The System Curve

Your duct system has its own resistance characteristic. Unlike the fan curve, the system curve is determined entirely by your installation: duct length, diameter, fitting count, and component pressure drops.

The system curve follows a quadratic relationship: pressure required increases approximately with the square of airflow (P ∝ Q²). Double the airflow, and the system requires roughly four times the static pressure.

The Operating Point

The operating point is where the fan curve and the system curve intersect. This is the only point where the fan can actually operate in your specific system — not the catalog condition, not the lab condition, but your actual installation. Airflow (CFM) → Static Pressure (in. wg) → ● OPERATING POINT 18,500 CFM @ 0.95 in. wg SP Fan Curve at constant RPM System Curve P ∝ Q² relationship 0 10K 20K 30K 40K 0 0.5 1.0 1.5 2.0 Fan Curve + System Curve = Operating Point The operating point (orange circle) is where the fan curve and the system resistance curve intersect. At this point the fan delivers 18,500 CFM at 0.95 in. wg — the actual field condition, not the catalog rating. This is the basis for fan selection, not published CFM ratings alone.

Why this matters: If the system resistance is higher than assumed during selection, the operating point shifts left along the fan curve — the fan delivers less air than designed, and the motor may overload trying to overcome the extra resistance. If resistance is lower, the fan operates to the right, potentially overloading the motor or causing excessive airflow and noise.

Variable Frequency Drives (VFDs) change this picture significantly. A VFD reduces the fan’s RPM, shifting the entire fan curve downward (following the fan laws: CFM ∝ RPM, Pressure ∝ RPM², Power ∝ RPM³). This enables the fan to operate along a family of curves, matching the system requirements at part-load conditions — which is where most industrial fans spend most of their operating hours.

[INTERNAL-LINK: Variable Frequency Drive (VFD) Fan Energy Savings: ROI Calculator & 3 Real-World Cases → VFD energy savings spoke article]


Fan Types and Their Selection Envelopes

The right fan type is determined by where your required CFM and static pressure fall within each type’s performance envelope. Selecting the wrong fan type — even with correct calculations — produces an inefficient, noisy, or short-lived installation.

Fan TypeCFM RangeStatic Pressure RangePeak EfficiencyBest Applications
Axial propeller500–100,000+0–0.5 in. wg40–60%General ventilation, cooling towers, temporary exhaust
Axial vane-axial1,000–80,0000.25–3.0 in. wg60–75%Ducted ventilation, tunnel ventilation, marine vessels
Centrifugal forward-curved200–20,0000.5–3.0 in. wg60–70%Commercial rooftop units, fan coils, clean airstreams
Centrifugal backward-inclined500–50,0000.5–6.0 in. wg70–80%VAV systems, industrial process, medium-pressure ducts
Centrifugal airfoil1,000–100,0001.0–10.0+ in. wg75–85%Industrial, cleanrooms, high-pressure systems
Plenum / housed VAV2,000–200,0000.5–8.0 in. wg70–82%Large commercial, variable air volume, low noise

For the warehouse ventilation example (20,000 CFM at ~0.95 in. wg), both a vane-axial fan and a backward-inclined centrifugal fan are technically suitable. The vane-axial offers higher efficiency at lower pressure, while the backward-inclined provides more stable performance across varying system conditions and is more tolerant of dirty airstreams.

Industrial centrifugal fan impeller and housing in a factory ventilation installation

[INTERNAL-LINK: Axial Fans vs Centrifugal Fans: 7 Key Differences Explained → comparison spoke article]


Application-Specific Selection Criteria

Beyond CFM, static pressure, and power, specific applications impose additional requirements that affect fan type, materials, and certifications. Ignoring these is one of the most common reasons for premature fan failure or safety incidents.

Hazardous Locations (ATEX / IECEx Zones)

In facilities where flammable gases, vapors, or dusts are present, fans must comply with IEC 60079 (Explosive Atmospheres) and either the ATEX Directive 2014/34/EU (Europe) or NFPA 70 / NEC Article 500 (North America). Fan motors must carry appropriate area classifications:

ZoneDefinitionTypical Motor Rating
Zone 0 (gas) / Zone 20 (dust)Continuous hazardExplosion-proof (XP) motor required
Zone 1 (gas) / Zone 21 (dust)Hazard likely in normal operationXP motor or increased safety
Zone 2 (gas) / Zone 22 (dust)Hazard only in abnormal conditionsNon-sparking motor acceptable

Spark-resistant construction — aluminum or non-ferrous impellers, static-safe drives, and clearance-controlled housings — is required in addition to motor classification.

[INTERNAL-LINK: Explosion-Proof Fan Selection: ATEX/IECEx Zones Explained → ATEX spoke article]

High-Temperature Applications

Standard fans are rated for airstream temperatures up to approximately 130°F (54°C). Processes exceeding 200°F (93°C) — smelting, forge exhaust, dryer ventilation, baking ovens — require fans with high-temperature materials, specialized bearings with extended lubrication intervals, and in some cases shaft cooling or bearing isolation.

The critical parameters are: airstream temperature, ambient temperature around the motor, bearing cooling method, and materials of construction ( shaft, impeller, housing, and seals must all be rated for the temperature).

[INTERNAL-LINK: High-Temperature Fan Applications: Selecting for 200°C+ Operations → high-temperature spoke article]

Cleanroom Applications

Cleanrooms require fans that deliver precise, consistent airflow with minimal turbulence to prevent particle resuspension. Key considerations include:

  • Airflow stability: ±5% variation or tighter at the operating point
  • Low outgassing: materials selected to minimize hydrocarbon release
  • Smooth internal surfaces: no ledges, pockets, or crevices where particles accumulate
  • Filter compatibility: the fan must be sized to overcome cleanroom HEPA or ULPA filter pressure drops (typically 0.5–1.5 in. wg clean, up to 2.5+ in. wg at end-of-life)

[INTERNAL-LINK: Smoke Extraction Fan Selection: NFPA 92 Compliance → smoke extraction spoke article]

Fire and Smoke Applications

Smoke extraction fans must comply with NFPA 92 (Standard for Smoke Control Systems) and are subject to specific requirements for construction materials, temperature ratings at fire conditions, and operational reliability. Stairwell pressurization fans, smoke control fans, and garage exhaust fans each carry different NFPA 92 classifications.


Common Fan Selection Mistakes and How to Avoid Them

Field performance audits of commercial and industrial HVAC installations consistently identify a recurring pattern: selection-stage errors — not manufacturing defects — account for the majority of fan performance shortfalls observed after startup. The five mistakes below represent the most common patterns found in post-installation performance testing across the industry.

Mistake 1: Using Catalog Free-Delivery Ratings Without System Resistance

The most common error. A fan cataloged at “25,000 CFM” achieves that only at zero external resistance. Every real installation has resistance. Always calculate static pressure from the actual duct system and find the operating point on the fan curve before selecting.

Fix: Calculate total system static pressure first. Then use the fan curve to find actual CFM at that pressure.

Mistake 2: Skipping the Motor Power Safety Factor

Calculating the exact HP required and specifying that exact motor size leaves no margin for voltage variation, elevated ambient temperature, or unexpected resistance. The motor will run hot and fail prematurely.

Fix: Always add 10–15% to calculated HP. Round up to the next standard motor size.

Mistake 3: Oversizing for “Future Expansion”

Adding 25–30% extra capacity “for growth” sounds prudent. It causes the fan to operate far to the right of its best efficiency point — producing excessive noise, high energy consumption, and poor part-load control. Variable frequency drives partially mitigate this but cannot fully correct a fundamentally oversized selection.

Fix: Size for current design conditions. Plan for future expansion as a separate fan or a VFD with headroom built into the motor, not into the fan curve position.

Mistake 4: Specifying the Wrong Fan Type for the System Curve Shape

Axial fans work well when the system curve is relatively flat (low resistance variation with flow). Centrifugal fans are more stable when the system curve is steep (resistance increases rapidly with flow). Selecting an axial fan for a high-resistance system, or vice versa, produces poor efficiency and unstable operation.

Fix: Match fan type to the expected system resistance profile. Centrifugal fans are more forgiving for typical HVAC systems.

Mistake 5: Ignoring Altitude and Temperature Effects on Air Density

Fan ratings are established at standard conditions (sea level, 68°F, 29.92 in. Hg barometric pressure). At altitude or elevated temperature, air density decreases. The fan’s ability to generate pressure is directly proportional to air density. A fan selected for Denver, Colorado (5,280 ft elevation) at design summer temperatures will deliver approximately 16–18% less pressure than its catalog rating — without accounting for this correction.

Fix: Apply a density correction factor. Approximate correction: reduce pressure capability by 3% per 1,000 ft of elevation, plus an additional correction for temperature above 68°F.

Pre-selection verification checklist:

  • [ ] Total system static pressure calculated from actual duct layout and components
  • [ ] Fan curve reviewed to confirm operating point falls in the fan’s highest-efficiency region
  • [ ] Motor HP calculated with 10–15% safety factor, rounded up to standard size
  • [ ] Fan type matched to system resistance profile
  • [ ] Altitude and temperature density corrections applied
  • [ ] Hazardous area, temperature, and cleanroom requirements verified before specifying

[INTERNAL-LINK: Industrial Fan Maintenance Checklist: 12-Point Guide → maintenance spoke article]

[INTERNAL-LINK: Industrial Fan Bearing Replacement: When & How → bearing replacement spoke article]


Frequently Asked Questions

What is the difference between CFM and SCMH?

CFM (cubic feet per minute) is the imperial unit for airflow. SCMH (standard cubic meters per hour) is the metric equivalent. 1 CFM ≈ 1.699 SCMH. Always verify which unit a specification is using before comparing — confusing the two can result in selecting a fan with roughly 70% of the required capacity.

How does altitude affect fan performance?

At higher altitudes, reduced air density decreases the fan’s ability to generate pressure. Above 2,000 ft elevation, apply a density correction factor of approximately 0.97 per 1,000 ft above sea level (multiply the catalog pressure by this factor). At 5,000 ft, a fan cataloged at 2.0 in. wg delivers approximately 1.85 × 0.97 = 1.79 in. wg at the altitude condition. Elevated temperatures cause additional density reduction.

What are the fan laws and how do they apply?

The fan laws describe how fan performance scales with changes in speed, diameter, and air density:

Fan LawRelationshipPractical Use
1st law (CFM)CFM₂ = CFM₁ × (RPM₂ / RPM₁)Predict CFM change from RPM change
2nd law (Pressure)SP₂ = SP₁ × (RPM₂ / RPM₁)²Predict pressure change from RPM change
3rd law (Power)HP₂ = HP₁ × (RPM₂ / RPM₁)³Predict power change from RPM change — this is the key to VFD savings

The cubic relationship in the 3rd law means halving fan RPM reduces power consumption to 1/8th — this is the basis for VFD energy savings.

When should I use a VFD on a fan?

Use a VFD whenever the load varies significantly across operating conditions: demand-controlled ventilation systems, multi-zone units with different loads, fans significantly oversized for peak conditions, or any application with significant part-load operation. A VFD also enables soft-start capability, reducing mechanical stress on the fan and drive system during startup.

What maintenance factors should affect my fan selection?

Consider bearing accessibility and expected replacement intervals (sealed bearings vs. relubricatable), motor replacement availability (standard NEMA frames vs. proprietary designs), and impeller cleanability for abrasive airstreams. In dirty or particulate-laden airstreams, select a fan with accessible bearings and cleanout ports to reduce maintenance cost and downtime.


Conclusion

Fan selection is a three-parameter system, not a single-specification decision. Start with airflow (CFM) from the room volume and ACH requirement, calculate static pressure from the actual duct system and components, then find the motor power needed to deliver that CFM at that pressure.

Five principles to follow on every selection:

  1. Calculate all three parameters together — CFM, static pressure, and HP are interdependent
  2. Always use the system resistance curve — never select from catalog free-delivery ratings alone
  3. Add a 10–15% safety factor to motor power and round up to the next standard size
  4. Match fan type to your application’s CFM and pressure envelope and system resistance profile
  5. Account for altitude, temperature, and special application requirements before finalizing the specification

Ready to specify a fan for your project? Use the calculation steps in this guide to verify your requirements. For custom industrial fans built to your exact specifications — including ATEX-rated, high-temperature, corrosion-resistant, or cleanroom-configured units — contact our engineering team to discuss your application requirements.